W - American Standard Steel Wide Flange Beams

ASTM A6 - Dimensions and static parameters of American steel wide flange beams - Imperial Units

astm a6 american wide flange steel beam

DesignationDepthWidthThickness WebThickness FlangeSectional AreaWeightMoment of Inertia - IxMoment of Inertia - IySection of Modulus - WxSection of Modulus - Wy
ininininin**2lb/ftin**4in**4in**3in**3
insert!W 27 x 17827.8114.0850.7251.19052.3178699055550278.8
insert!W 27 x 16127.5914.0200.6601.08047.4161628049745570.9
insert!W 27 x 14627.3813.9650.6050.97542.9146563044341163.5
insert!W 27 x 11427.2910.0700.5700.93033.5114409015929931.5
insert!W 27 x 10227.0910.0150.5150.83030.0102362013926727.8
insert!W 27 x 9426.929.9900.4900.74527.794327012424324.8
insert!W 27 x 8426.719.9600.4600.64024.884285010621321.2
insert!W 24 x 16225.0012.9550.7051.22047.7162517044341468.4
insert!W 24 x 14624.7412.9000.6501.09043.0146458039137160.5
insert!W 24 x 13124.4812.8550.6050.96038.5131402034032953.0
insert!W 24 x 11724.2612.8000.5500.85034.4117354029729146.5
insert!W 24 x 10424.0612.7500.5000.75030.6104310025925840.7
insert!W 24 x 9424.319.0650.5150.87527.794270010922224.0
insert!W 24 x 8424.109.0200.4700.77024.784237094.419620.9
insert!W 24 x 7623.928.9900.4400.68022.476210082.517618.4
insert!W 24 x 6823.738.9650.4150.58520.168183070.415415.7
insert!W 24 x 6223.747.0400.4300.59018.262155034.51319.8
insert!W 24 x 5523.577.0050.3950.50516.255135029.11148.3
insert!W 21 x 14722.0612.5100.7201.15043.2147363037632960.1
insert!W 21 x 13221.8314.4400.6501.03538.8132322033329553.5
insert!W 21 x 12221.6812.3900.6000.96035.9122296030527349.2
insert!W 21 x 11121.5112.3400.5500.87532.7111267027424944.5
insert!W 21 x 10121.3612.2900.5000.80029.8101242024822740.3
insert!W 21 x 9321.628.4200.5800.93027.393207092.919222.1
insert!W 21 x 8321.438.3550.5150.83524.383183081.417119.5
insert!W 21 x 7321.248.2950.4550.74021.573160070.615117.0
insert!W 21 x 6821.138.2700.4300.68520.068148064.714015.7
insert!W 21 x 6220.998.2400.4000.61518.362133057.512713.8
insert!W 21 x 5721.066.5550.4050.65016.757117030.61119.35
insert!W 21 x 5020.836.5300.3800.53514.75098424.494.57.64
insert!W 21 x 4420.666.5000.3500.45013.04484320.781.66.36
insert!W 18 x 11918.9711.2650.6551.06035.1119219025323144.9
insert!W 18 x 10618.7311.2000.5900.94031.1106191022020439.4
insert!W 18 x 9718.5911.1450.5350.87028.597175020118836.1
insert!W 18 x 8618.3911.0900.4800.77025.386153017516631.6
insert!W 18 x 7618.2111.0350.4250.68022.376133015214627.6
insert!W 18 x 7118.477.6350.4950.81020.871117060.312715.8
insert!W 18 x 6518.357.5900.4500.75019.165107054.811714.4
insert!W 18 x 6018.247.5550.4150.69517.66098450.110813.3
insert!W 18 x 5518.117.5300.3900.63016.25589044.998.311.9
insert!W 18 x 5017.997.4950.3550.57014.75080040.188.910.7
insert!W 18 x 4618.096.0600.3600.60513.54671222.578.87.43
insert!W 18 x 4017.906.0150.3150.52511.84061219.168.46.35
insert!W 18 x 3517.706.0000.3000.42510.33551015.357.65.12
insert!W 16 x 10016.9710.4250.5850.98529.4100149018617535.7
insert!W 16 x 8916.7510.3650.5250.87526.289130016315531.4
insert!W 16 x 7716.5210.2950.4550.76022.677111013813426.9
insert!W 16 x 6716.3310.2350.3950.66519.76795411911723.2
insert!W 16 x 5716.437.1200.4300.71516.85775843.192.212.1
insert!W 16 x 5016.267.0700.3800.63014.75065937.281.010.5
insert!W 16 x 4516.137.0350.3450.56513.34558632.872.79.34
insert!W 16 x 4016.016.9950.3050.50511.84051828.964.78.25
insert!W 16 x 3615.866.9850.2950.43010.63644824.556.57.00
insert!W 16 x 3115.885.5250.2750.4409.123137512.447.24.49
insert!W 16 x 2615.695.5000.2500.3457.68263019.5938.43.49
insert!W 14 x 73022.4217.8903.0704.9102157301430047201280527
insert!W 14 x 66521.6417.6502.8304.5201966651240041701150472
insert!W 14 x 60520.9217.4152.5954.1601786051080036801040423
insert!W 14 x 55020.2417.2002.3803.82016255094303250931378
insert!W 14 x 50019.6017.0102.1903.50014750082102880838339
insert!W 14 x 45519.0216.8352.0153.21013445571902560756304
insert!W 14 x 42618.6716.6951.8753.03512542666002360707283
insert!W 14 x 39818.2916.5901.7702.84511739860002170656262
insert!W 14 x 37017.9216.4751.6552.66010937054401990607241
insert!W 14 x 34217.5716.3601.5402.47010134249001810559221
insert!W 14 x 31117.1216.2301.4102.26091.431143301610506199
insert!W 14 x 28316.7416.1101.2902.07083.328338401440459179
insert!W 14 x 25716.3815.9951.1751.89075.625734001290415161
insert!W 14 x 23316.0415.8901.0701.72068.523330101150375145
insert!W 14 x 21115.7215.8000.9801.56062.021126601030338130
insert!W 14 x 19315.4815.7100.8901.44056.81932400931310119
insert!W 14 x 17615.2215.6500.8301.31051.81762140838281107
insert!W 14 x 15914.9815.5650.7451.19046.7159190074825496.2
insert!W 14 x 14514.7815.5000.6801.09042.7145171067723287.3
insert!W 14 x 13214.6614.7250.6451.03038.8132153054820974.5
insert!W 14 x 12014.4814.6700.5900.94035.3120138049519067.5
insert!W 14 x 10914.3214.6050.5250.86032.0109124044717361.2
insert!W 14 x 9914.1614.5650.4850.78029.199111040215755.2
insert!W 14 x 9014.0214.5200.4400.71026.59099936214349.9
insert!W 14 x 8214.3110.1300.5100.85524.18288214812329.3
insert!W 14 x 7414.1710.0700.4500.78521.87479613411226.6
insert!W 14 x 6814.0410.0350.4150.72020.06872312110324.2
insert!W 14 x 6113.899.9950.3750.64517.96164010792.221.5
insert!W 14 x 5313.928.0600.3700.66015.65354157.777.814.3
insert!W 14 x 4813.798.0300.3400.59514.14848551.470.312.8
insert!W 14 x 4313.667.9950.3050.53012.64342845.262.711.3
insert!W 14 x 3814.106.7700.3100.51511.23838526.754.67.88
insert!W 14 x 3413.986.7450.2850.45510.03434026.348.66.91
insert!W 14 x 3013.846.7300.2700.3858.853029119.642.05.82
insert!W 14 x 2613.915.0250.2550.4207.69262458.9135.33.54
insert!W 14 x 2213.745.0000.2300.3356.49221997.0029.02.80
insert!W 12 x 33616.8213.3851.7752.95598.833640601190483177
insert!W 12 x 30516.3213.2351.6252.70589.630535501050435159
insert!W 12 x 27915.8513.1401.5302.47081.92793110937393143
insert!W 12 x 25215.4113.0051.3952.25074.12522720828353127
insert!W 12 x 23015.0512.8951.2852.07067.72302420742321115
insert!W 12 x 21014.7112.7901.1801.90061.82102140664292104
insert!W 12 x 19014.3812.6701.0601.73555.8190189058926393.0
insert!W 12 x 17014.0312.5700.9601.56050.0170165051723582.3
insert!W 12 x 15213.7112.4800.8701.40044.7152143045420972.8
insert!W 12 x 13613.4112.4000.7901.25039.9136124039818664.2
insert!W 12 x 12013.1212.3200.7101.10535.3120107034516356.0
insert!W 12 x 10612.8912.2200.6100.99031.210693330114549.3
insert!W 12 x 9612.7112.1600.5500.90028.29683327013144.4
insert!W 12 x 8712.5312.1250.5150.81025.68774024111839.7
insert!W 12 x 7912.3812.0800.4700.73523.27966221610735.8
insert!W 12 x 7212.2512.0400.4300.67021.17259719597.432.4
insert!W 12 x 6512.1212.0000.3900.60519.16553317487.929.1
insert!W 12 x 5812.1910.0100.3600.64017.05847510778.021.4
insert!W 12 x 5312.069.9950.3450.57515.65342595.870.619.2
insert!W 12 x 5012.198.0800.3700.64014.75039456.364.713.9
insert!W 12 x 4512.068.0450.3350.57513.24535050.058.112.4
insert!W 12 x 4011.948.0050.2950.51511.84031044.151.911.0
insert!W 12 x 3512.506.5600.3000.52010.33528524.545.67.47
insert!W 12 x 3012.346.5200.2600.4408.793023820.338.66.24
insert!W 12 x 2612.226.4900.2300.3807.652620417.333.45.34
insert!W 12 x 2212.314.0300.2600.4256.48221564.6625.42.31
insert!W 12 x 1912.164.0050.2350.3505.57191303.7621.31.88
insert!W 12 x 1611.993.9900.2200.2654.71161032.8217.11.41
insert!W 12 x 1411.913.9700.2000.2254.161488.62.3614.91.19
insert!W 10 x 11211.3610.4150.7551.25032.911271623612645.3
insert!W 10 x 10011.1010.3400.6801.12029.410062320711240.0
insert!W 10 x 8810.8410.2650.6050.99025.98853417998.534.8
insert!W 10 x 7710.6010.1900.5300.87022.97745515485.930.1
insert!W 10 x 6810.4010.1300.4700.77020.06839413475.726.4
insert!W 10 x 6010.2210.0800.4200.68017.66034111666.723.0
insert!W 10 x 5410.0910.0300.3700.61515.85430310360.020.6
insert!W 10 x 499.9810.0000.3400.56014.44927293.454.618.7
insert!W 10 x 4510.108.0200.3500.62013.34524853.449.113.3
insert!W 10 x 399.927.9850.3150.53011.53920945.042.111.3
insert!W 10 x 339.737.9600.2900.4359.713317036.635.09.20
insert!W 10 x 3010.475.8100.3000.5108.843017016.732.45.75
insert!W 10 x 2610.335.7700.2600.4407.612614414.127.94.89
insert!W 10 x 2210.175.7500.2400.3606.492211811.423.23.97
insert!W 10 x 1910.244.0200.2500.3955.621996.34.2918.82.14
insert!W 10 x 1710.114.0100.2400.3304.991781.93.5616.21.78
insert!W 10 x 159.994.0000.2300.2704.411568.92.8913.81.45
insert!W 10 x 129.873.9600.1900.2103.541253.82.1810.91.10
insert!W 8 x 679.008.2800.5700.93519.76727288.660.421.4
insert!W 8 x 588.758.2200.5100.81017.15822875.152.018.3
insert!W 8 x 488.508.1100.4000.68514.14818460.943.315.0
insert!W 8 x 408.258.0700.3600.56011.74014649.135.512.2
insert!W 8 x 358.128.0200.3100.49510.33512742.631.210.6
insert!W 8 x 318.007.9950.2850.4359.133111037.127.59.27
insert!W 8 x 288.066.5350.2850.4658.252898.021.724.36.63
insert!W 8 x 247.936.4950.2450.4007.082482.818.320.95.63
insert!W 8 x 218.285.2700.2500.4006.162175.39.7718.23.71
insert!W 8 x 188.145.2500.2300.3305.261861.97.9715.23.04
insert!W 8 x 158.114.0150.2450.3154.441548.03.4111.81.70
insert!W 8 x 137.994.0000.2300.2553.841339.62.739.911.37
insert!W 8 x 107.893.9400.1700.2052.961030.82.097.811.06
insert!W 6 x 256.386.0800.3200.4557.342553.417.1016.75.61
insert!W 6 x 206.206.0200.2600.3655.872041.413.3013.44.41
insert!W 6 x 166.284.0300.2600.4054.741632.14.4310.22.20
insert!W 6 x 155.995.9900.2300.2604.431529.19.329.723.11
insert!W 6 x 126.034.0000.2300.2803.551222.12.997.311.50
insert!W 6 x 95.903.9400.1700.2152.68916.42.195.561.11
insert!W 5 x 195.155.0300.2700.4305.541926.29.1310.23.63
insert!W 5 x 165.015.0000.2400.3604.681621.37.518.513.00
insert!W 4 x 134.164.0600.2800.3453.831311.33.865.461.90
custom!
DesignationDepthWidthThickness WebThickness FlangeSectional AreaWeightMoment of Inertia - IxMoment of Inertia - IySection of Modulus - WxSection of Modulus - Wy
ininininin**2lb/ftin**4in**4in**3in**3


Sponsored Links

Tools - accessed from within SketchUp

The insert! and the Tools features works only from the inside of SketchUp. Add and edit parametric objects to the SketchUp model!

Edit:
undo - redo

Color:
change color! - of the selected object(s) - may be slow for some more complicated objects (save your model first!)

View:
iso - top - front - right - left - back - bottom

Make Component:
make! a component of the selected object. Note that all objects from the Engineering Toolbox are inserted as individual groups. You should transfer a group to a component sharing the same definition when there is more than one instance of the same object. Tips! Rename the object to its final name before making it a component (in outliner or with right click and entity info).

Rotate Object(s):
degrees around red, green or blue axis! (select object(s) first)

Move or Copy Object(s): - move or copy (multiple) selected objects
move/copy! no. copies red green blue (offset from current position)
Make advanced geometric constructions with multiple selections, multiple copies and the offset.
Tip! - Use "Make Component" to save space and reduce computer load when working with multiple copies.

New! Move an Object to an other Objects Position
move! Select two objects - click "move" and one of the objects moves to the position and angle of the other object. Handy when moving between axis systems.

New! Change Insertion Point
You can change the position and angle of an inserting object by pre-selecting an existing object before Insert! The inserted object will inherit the position of the selected object. Handy when working with non-default axis.

Insert Line: - use this feature to add reference lines
red green blue - Start position
red green blue - End position
insert!

Insert Horizontal Plane: - use this feature to add reference planes
insert! red (size) green (size) blue (vertical position)

Insert Vertical Plane: - use this feature to add reference planes
insert! red (horizontal position) green (size) blue (vertical size)
insert! red (size) green (horizontal position) blue (vertical size)

Insert Box: - add a box
insert! red (width) green (depth) blue (height)

Insert external Component: - add an external component from the internet by adding the component url
insert! name url

10 3 13

Sponsored Links